Multiple NM-B Cables through a 2" EMT Conduit (NEC 2002)

By Warren Goodrich
Multiple NM-B Cables through a 2" EMT Conduit (NEC 2002)

This article is purely academic. The situation I present does not actually exist. I'd just like to discuss how such calculations are made.

Hypothetically, I want to put a bunch of 12/2 NM-B cables through a 2" EMT conduit.

The first question is how many 12/2 cables I'm allowed to put through this 2" EMT.

We head to Chapter 9 of the 2002 NEC for the answer. Table 4 says that a 2" EMT conduit has a total area of 3.356 square inches. Table 1 says that I can only fill this cable to 40% if I have over 2 conductors. Back to Table 4 says that 40% of the conduit is 1.342 square inches.

12/2 NM-B cable is 1/2" wide. Note (9) says I must treat this as a 1/2" round cable. Using pi*r*r, I compute the cable has a cross section of 0.196 square inches. Dividing 1.342 by 0.196 says I can put 6.83 cables in this conduit. Note (7) tells me that since the decimal is above 0.8, I can round this up to 7.

So the answer to the first question is seven. So far so good?

Now the second question is what size breaker I'm allowed to put on these seven 12/2 cables.

So we go to Section 310 of the 2002 NEC.

Table 310.15(B)(2)(a) gives me adjustment factors for more than three current-carrying conductors in a raceway. Since I have seven 12/2 cables, I figure I have 14 current-carrying conductors. The table tells me that for 10 to 20 conductors, I just use only 50% of the ampacity determined by tables 310.16 through 310.19.

So now I head for table 310.16. This table tells me that THHN wire (which is what 12/2 NM-B is made from) has an ampacity of 30 amps when I have not more than three conductors. I will assume an ambient temperature of 86 degrees F so that I need not make an ambient temperature correction. Taking 50% of the 30 amps gives me 15 amps. Since 15 amps is less than the 60 degree rating of 12-gauge copper as per 110.14.C.1.A, I may use the 15 amp rating for my 12/2wGrnd NM-B conductor.

So the answer to the second question is a 15-amp breaker.

This document is based on the 2002 national electrical code and is designed to give you an option, as a self - help, that should pass minimum code requirements. While extensive research has been implemented in the preparation of this self - help document, the author and / or provider of this document assumes no responsibility for errors or omissions, nor is any liability assumed from the use of the information contained within this document by the author or provider.

Find a Pre-Screened Electrician
Enter Your Zip Code:


THIS ARTICLE IS PROVIDED 'AS IS' WITH NO WARRANTY OF ANY KIND. THE AUTHOR, THE SITE OWNER AND ITS AFFILIATES ASSUME NO LIABILITY FOR ERRORS OR OMISSIONS CONTAINED THEREIN OR FOR ANY USE OF THE INFORMATION CONTAINED IN THIS DOCUMENT. The article is for informational purposes only and is not a substitute for professional advice.