| |
|
|
|
|
|
|
|
|
|
|
|
| |
GENERAL METHOD OF DWELLING CALCULATION |
|
| |
WRITTEN 7/1/94 |
|
| LAST REVISE 7/9/01 |
|
BY WARREN GOODRICH |
|
| |
| THIS DOCUMENT IS BASED ON THE 1999 NATIONAL ELECTRICAL CODE AND IS DESIGNED TO GIVE YOU AN OPTION, AS |
|
| A SELF HELP, THAT SHOULD PASS MINIMUM CODE REQUIREMENTS. WHILE EXTREME CARE HAS BEEN IMPLEMENTED |
|
| IN THE PREPARATION OF THIS SELF HELP DOCUMENT. THE AUTHOR AND / OR PROVIDER OF THIS DOCUMENT |
|
| ASSUMES NO RESPONSIBILITY FOR ERRORS, OR OMISSIONS, NOR IS ANY LIABILITY ASSUMED FROM THE USE OF |
|
| THE INFORMATION CONTAINED WITH THIS IiOCUMENT, BY THE AUTHOR, OR PROVIDER |
|
| |
| 220-3A LIGHTING LOAD [3 Va]. X OUTSIDE DIMENSIONS OF YOUR BUILDINGS ON THAT SERVICE. [REQUIRED] |
|
| |
| 220-16-A ADD IN 3,000 Va FOR SMALL APPLIANCE BRANCH CIRCUITS FOR THE DWELLING. [REQUIRED] |
|
| |
| 220-16-B ADD IN 1,500 Va FOR LAUNDRY IN THE DWELLING WHETHER USED OR NOT. [REQUIRED] |
|
| |
| |
ADD FROM HERE DOWN WHEN FINDING THE TOTAL DEMAND LOAD OF THE DWELLING |
|
| |
| 220-11 APPLY GENERAL LIGHTING DEMAND FACTOR TO THE TOTAL OF THE ABOVE 3 STEPS. THIS WILL BE |
|
| |
YOUR STARTING POINT FROM HERE. |
[DO NOT ADD THE FIRST 3 STEPS TO THIS GENERAL LIGHTING |
|
| |
DEMAND FACTOR] |
THIS STEP IS THE STARTING OVER ADJUSTED CALCULATION OF THE |
|
| |
FIRST 3 STEPS ARRIVING AT THE ADJUSTED GENERAL LIGHTING DEMAND LOAD. |
|
| |
| 220-21 ENTER THE LARGER OF THE HEAT AND A/C IN Va. |
|
[A/C - VERSUS - HEAT ] {Va. = APPROXIMAT WATTS} |
|
| |
| 220-17 LIST FASTENED IN PLACE APPLIANCE, AND TOTAL THE VA. / IF 3 OR LESS APPLIANCES, THEN ENTER AT |
|
| |
AT 100 % / IF THERE ARE FOUR, OR MORE APPLIANCES, ON LIST OF FASTENED IN PLACE APPLIANCES, |
|
| |
ENTER AT 75 % OF THE TOTAL SUM OF APPLIANCES Va. THIS WILL, NOW BE, YOUR ADJUSTED DEMAND |
|
| |
LOAD, CONCERNING ALL OF THE FASTENED IN PLACE APPLIANCES Va. |
[Va. = APPROXIMAT WATTS] |
|
| |
| 220-18 ENTER CLOTHES DRYER AT 5000 Va. / OR NAME PLATE RATING WHICH EVER IS LARGER, REGARDLESS OF |
|
| |
THE ACTUAL LOAD OF LESS THAN 5000 VA. IF ONLY ONE DRYER IS USED. |
|
| |
5000 Va. IS THE MINIMUM LOAD CALCULATION ALLOWED. |
|
| |
| 220-19 APPLY HOUSEHOLD COOKING EQUIPMENT TOTAL NUMBER OF ALL COOKING EQUIPMENT TO |
|
| |
DEMAND FACTOR, IN Va., AND ENTER THE PRODUCT OF THAT CALCULATION PROVIDED IN THE CHART |
|
| |
| 220-14 & 430-24 FIND THE LARGEST MOTOR INVOLVED, AND MULTIPLY THAT MOTOR’S FULL LOAD |
|
| |
CURRENT (FLC) BY 25 %, AND ENTER THAT FIGURE. |
|
| |
| |
FINAL CALCULATON AS FOLLOWS; |
|
| |
| |
THE TOTAL OF ALL OF THE ABOVE CALCULATIONS, WITH THE EXCEPTIONS OF THE FIRST 3 STEPS, |
|
| |
WILL GIVE YOU THE TOTAL Va. |
[APPROXIMATE WATTS] |
DEMAND OF THE HOME, THEN DIVIDE THE |
|
| |
TOTAL Va. |
[APPROXIMATE WATTS] |
BY THE SUPPLY VOLTAGE TO FIND THE DEMAND LOAD, IN AMPS. |
|
| |
THEN REFER TO ARTICLE 240 / 6, IN THE NEC, TO FIND THE MINIMUM BREAKER, OR FUSE, SIZE |
|
| |
REQUIRED FOR THE MAIN SERVICE PANEL. NOW REFER TO CHART 310/16 NOTE # 3 TO FIND THE |
|
| |
MINIMUM SERVICE FEEDER CONDUCTOR SIZE. |
|
| |
| |
USE [TABLE 250-94] FOR SIZING THE GROUNDING ELECTRODE CONDUCTOR. |
|
| |
| |
GENERAL METHOD OF DWELLING CALCULATION |
|
| |
FOR NEUTRAL CONDUCTOR SIZING |
|
| |
| 220-3A LIGHTING LOAD [3 Va]. X OUTSIDE DIMENSIONS OF YOUR BUILDINGS ON THAT SERVICE. [REQUIRED] |
|
| |
| 220-16-A ADD IN 3,000 Va FOR SMALL APPLIANCE BRANCH CIRCUITS FOR THE DWELLING. [REQUIRED] |
|
| |
| 220-16-B ADD IN 1,500 Va FOR LAUNDRY IN THE DWELLING WHETHER USED OR NOT. [REQUIRED] |
|
| |
| |
| |
ADD FROM HERE DOWN WHEN FINDING THE TOTAL DEMAND LOAD OF THE DWELLING |
|
| |
| 220-11 APPLY GENERAL LIGHTING DEMAND FACTOR TO THE TOTAL OF THE ABOVE 3 STEPS. THIS WILL BE |
|
| |
YOUR STARTING POINT FROM HERE. |
[DO NOT ADD THE FIRST 3 STEPS TO THIS GENERAL LIGHTING |
|
| |
DEMAND FACTOR] |
THIS STEP IS THE STARTING OVER ADJUSTED CALCULATION OF THE |
|
| |
FIRST 3 STEPS ARRIVING AT THE ADJUSTED GENERAL LIGHTING DEMAND LOAD. |
|
| |
| INSTALL THE HEAT OR AIR CONDITIONER/USING ONLY THE PART OF THE LOAD THAT IS CARRIED ON THE NEUTRAL / 120 V LOAD |
|
| 220-21 ENTER THE LARGER OF THE HEAT AND A/C IN Va. |
|
[A/C - VERSUS - HEAT ] {Va. = APPROXIMAT WATTS} |
|
| |
IF EITHER, THE HEAT OR A/C USES THE NEUTRAL, OR BOTH, THEN USE THE LARGEST NEUTRAL LOAD ONLY. |
|
| 220-17 LIST FASTENED IN PLACE APPLIANCE, AND TOTAL THE VA. / IF 3 OR LESS APPLIANCES, THEN ENTER AT |
|
| |
AT 100 % / IF THERE ARE FOUR, OR MORE APPLIANCES, ON LIST OF FASTENED IN PLACE APPLIANCES, |
|
| |
ENTER AT 75 % OF THE TOTAL SUM OF APPLIANCES Va. THIS WILL, NOW BE, YOUR ADJUSTED DEMAND |
|
| |
LOAD, CONCERNING ALL OF THE FASTENED IN PLACE APPLIANCES Va. |
[Va. = APPROXIMAT WATTS] |
|
| THIS 25% REDUCTION IS USED, ONLY IF, MORE THAN 3 FASTENED IN PLACE APPLIANCE USES THE NEUTRAL CONDUCTOR |
|
| |
USING ONLY THOSE LOADS THAT ARE ON THE NEUTRAL. / ADJUSTED BY 25% LESS, ONLY IF, THERE IS MORE THAN |
|
| |
3 FIXED APPL. LOADS ON THE NEUTRAL |
|
| 220-18 ENTER CLOTHES DRYER AT 5000 Va. / OR NAME PLATE RATING WHICH EVER IS LARGER, REGARDLESS OF |
|
| |
THE ACTUAL LOAD OF LESS THAN 5000 VA. IF ONLY ONE DRYER IS USED. |
|
| |
5000 Va. IS THE MINIMUM LOAD CALCULATION ALLOWED. |
|
| YOUR MAY USE A 30% REDUCTION FOR THE NEUTRAL LOAD, REGARDLESS OF THE ACTUAL LOAD CARRIED. |
|
| 220-19 / 220-22 APPLY HOUSEHOLD COOKING EQUIPMENT TOTAL NUMBER OF ALL COOKING EQUIPMENT TO |
|
| |
DEMAND FACTOR, IN Va., AND ENTER THE PRODUCT OF THAT CALCULATION PROVIDED IN THE CHART |
|
| YOUR MAY USE A 30% REDUCTION FOR THE NEUTRAL LOAD, REGARDLESS OF THE ACTUAL LOAD CARRIED. |
|
| 220-14 & 430-24 FIND THE LARGEST MOTOR INVOLVED, AND MULTIPLY THAT MOTOR’S FULL LOAD |
|
| |
CURRENT (FLC) BY 25 %, AND ENTER THAT FIGURE. |
|
| APPLY THE NEUTRAL LOAD, ONLY IF, THERE ARE MOTOR LOADS ON THE FEEDER THAT USES A NEUTRAL |
|
| |
| |
FINAL CALCULATON AS FOLLOWS; |
|
| |
| THE TOTAL OF ALL OF THE ABOVE CALCULATIONS, WITH THE EXCEPTIONS OF THE FIRST 3 STEPS, WILL GIVE YOU |
|
| THE TOTAL Va. |
[APPROXIMATE WATTS] |
NEUTRAL DEMAND OF THE DWELLING, THEN DIVIDE THE TOTAL Va. |
|
| [APPROXIMATE WATTS] |
BY THE SUPPLY VOLTAGE TO FIND THE NEUTRAL DEMAND LOAD, IN AMPS. THEN REFER |
|
| TO ARTICLE 220-22, IN THE NEC, TO ALLOW A FURTHER REDUCTION OF 30 % OF THE REMAINING NEUTRAL LOAD THAT |
|
| IS OVER 200 AMPS. |
NOW REFER TO TABLE 310-16 TO SIZE THE NEUTRAL CONDUCTOR TO THE PRODUCT OF THE |
|
| NEUTRAL DEMAND LOAD, THAT YOU HAVE JUST CALCULATED. |
|
| |
| REMEMBER THAT YOU MAY NOT SIZE THE NEUTRAL SMALLER THAN THE GROUNDING ELECTRODE CONDUCTOR |
|
| SIZED USING TABLE 250-66. |
YOU CAN FIND THIS MINIMUM SIZE NEUTRAL CONDUCTOR REQUIREMENT, REGARDING |
|
| THE GROUNDING CONDUCTOR IN ARTICLE 250-24-B-1. |
ALSO THE NEUTRAL CONDUCTOR IS NOT ALLOWED MORE |
|
| THAN 12 1/2% IN CIRCULAR MILL IN AREA THAN THE CIRCULAR MILL IN AREA OF THE UNGROUNDED {HOT} CONDUCTOR. |
|
| |
| |
USE [TABLE 250-94] FOR SIZING THE GROUNDING ELECTRODE CONDUCTOR. |
|
| |
| |
EXAMPLE DWELLING CALCULATION |
|
| |
| LIVING AREA |
25' X 60' |
[OUTSIDE DIMENSIONS] |
|
| 5 HP 1 PH 240 VOLT A/C MOTOR |
|
| 10 KW ELECTRIC SPACE HEAT 240 VOLT |
|
| 14 KW RANGE 240 VOLT / 120 VOLT |
|
| 4 KW WATER HEATER |
|
| 4 KW CLOTHES DRYER 240 VOLT / 120 VOLT |
|
| 2 KW DISHWASHER 120 VOLT |
|
| 1/2 H.P. COMPACTOR 120 VOLT |
|
| 1/3 H,P. DISPOSAL 120 VOLT |
|
| 1 H.P. POOL PUMP 240V |
|
LINE CONDUCTORS |
NEUTRAL CONDUCTOR |
|
| |
| 1,500 SQ., FEET X '3 va |
|
4,500 |
va. |
4,500 |
va. |
|
| SMALL APPLIANCE 2 X 1,500 va. |
|
3,000 |
va. |
3,000 |
va. |
|
| LAUNDRY 1 X 1,500 va. |
|
1,500 |
va. |
1,500 |
va. |
|
| |
9,000 |
va. |
9,000 |
va. |
|
| LIGHTING DEMAND: |
|
|
|
|
|
| |
1st 3,000 va. @ 100% |
|
3,000 |
va. |
3,000 |
va. |
|
| |
REMAINING 6,000 va. @ 35% |
|
2,100 |
va. |
2,100 |
va. |
|
| |
5,100 |
va. |
5,100 |
va. |
|
| 5 H.P. A/C 28 AMP X 240 VOLT = 6,720 va. |
( SMALLER THAN 10 Kw. HEAT ) |
OMIT A/C {SMALLER THAN HEAT |
|
| 10 Kw. HEAT |
[ OMIT THE A/C BECAUSE IT IS THE SMALLEST LOAD ] |
10,000 |
va. |
- |
va. |
|
| 3Kw. WATER HEATER |
( 75 % AT FINAL TOTAL ) |
{ MORE THAN 3 FASTENED APPL. } |
3,000 |
va. |
- |
va. |
|
| SPECAIL NOTE |
{ NORMALLY WATER HEATERS HEAT ONLY ONE ELEMENT AT A TIME } |
va. |
|
|
| 2 Kw. DISHWASHER |
{MOTOR PLUS ELEMENT} |
{ 120 VOLT } |
1,500 |
va. |
1,500 |
va. |
|
| COMPACTOR |
( 9. 8 AMPS X 120 VOLTS = 1,176 va. X '75% ) |
|
882 |
va. |
882 |
va. |
|
| DISPOSAL |
|
( 7.2 AMPS X 120 VOLTS = 864 va. X 75% ) |
|
648 |
va. |
648 |
va. |
|
| WATER PUMP |
( 8.0 AMPS X 240 VOLTS = 1,920 va. X 75% ) |
|
1,440 |
va. |
- |
va. |
|
| 4 Kw. DRYER = |
( 5 Kw. MINIMUM ) |
{ 240 / 120 VOLT } |
{ MOTOR = 120 } |
5,000 |
REDUCE 30% --> |
3,500 |
va. |
|
| l4 Kw. RANGE |
( TABLE 220 - 19 NOTE 1 ) |
{ 240 / 120 VOLT } |
{BULB/CLOCK120v} |
8,800 |
REDUCE 30% --> |
6,160 |
va. |
|
| LARGEST MOTOR |
( 9.8 AMPS X 120 VOLTS = 1,176 X 25%) |
|
294 |
va. |
294 |
va. |
|
| |
36,664 |
va. |
18,084 |
va. |
|
| LINE = |
36,664 |
va. |
152.77 |
AMPS |
{ EXTRA 30% REDUCTION ALLOWED ON NEUTRAL FEEDER LOAD IN EXCESS OF 200 AMPS } |
| |
240 |
volts |
310/16 NOTE 3 = |
1/0 CU. |
FEEDER |
(REMAINING OVER 200 AMPS) |
X 70 % |
|
| USING 240/6 TO NEXT LARGEST OVERCURRENT DEVICE |
{BREAKER OR FUSE} |
|
NO REDUCTION |
|
| ADJUSTED TO MEET NEC MINIMUMS = |
175 |
amps |
{UNGROUNDED CONDUCTOR} (HOT) |
18,084 |
va. |
|
| NEUTRAL = |
18,084 |
va. |
|
| |
240 |
volts = |
75.35 |
AMPS |
310/16 -250/94 = |
# 4 THHN CU. NEUTRAL FEEDER |
|
| |
{ NEUTRAL IS NOT ALLOWED TO BE SMALLER THAN THE GROUNDING CONDUCTOR } |
|
| GROUNDING ELECTRODE CONDUCTOR |
|
| SPECIAL NOTES: |
|
| |
YOU MUST SIZE THE DWELLING SERVICE ENTRANCE UNGROUNDED CONDUCTOR |
{ HOT } |
|
| |
BY USING THE TABLE FOUND IN THE NEC. THIS TABLE CAN BE FOUND IN ARTICLE |
|
| |
310/15-B-6, USING THE TOTAL DEMAND LOAD YOU JUST CALCULATED. |
|
| |
AND ARTICLE 240/6 TO SIZE THE MAIN SERVICE OVERCURRENT DEVICE |
BREAKER / FUSE |
|
| |
YOU MUST SIZE THE DWELLING SERVICE ENTRANCE GROUNDED CONDUCTOR |
|
{ NEUTRAL } |
|
| |
BY USING THE TABLE FOUND IN THE NEC. THIS TABLE CAN BE FOUND IN ARTICLE |
|
| |
310/16, AND THE TOTAL NEUTRAL DEMAND LOAD YOU JUST CALCULATED. |
{BOLD PRINT } |
|
| ATTENTION: |
|
| |
THE NEUTRAL MAY NOT BE SMALLER THAN THE GROUNDING CONDUCTOR |
{BARE OR GREEN} |
|
| |
FOR SIZING THE SERVICE ENTRANCE NEUTRAL CONDUCTOR. |
|
| |
|
|
|
|
|
|
|
|
|
|
|